These Distributed Safety I/O Terminals are designed for robust industrial automation, allowing system integrators to monitor and control safety functions across networks while significantly reducing complex wiring. Certified to rigorous standards including IEC 61508 SIL3 and ISO13849-1 (PLe), the modules ensure high reliability in critical applications. This manual provides comprehensive technical specifications, connectivity details, configuration guidelines, and detailed performance data for various models (including relay and semiconductor outputs). It is essential reading for automation engineers specifying safety control solutions that require maximum uptime and low risk.

📄 Preview PAGE OF 5

Page 1 Text Content

Safety I/O Terminals

DST1 Series

CSM_DST1 Series_DS_E_7_4

Distributed Safety Terminals That Reduce Wiring. Lineup includes four models to accommodate various I/O types and number of I/O points. Monitor the safety system from Standard Controllers across the network. EN954-1 (Cat.4), ISO13849-1 (PLe), and IEC 61508 SIL3 certification. The DST1-XD0808SL-1 also supports logic operation functions for high-speed processing in applications requiring partial stopping of the safety system.

Ordering Information List of Models Name No. of I/O points Model

Safety inputs: 12, test outputs: 4 DST1-ID12SL-1

DST1-MD16SL-1

Safety I/O Terminals Safety inputs: 8, safety outputs (semiconductor): 8, test outputs: 4

DST1-XD0808SL-1 *

Safety inputs: 4, safety outputs (relay): 4, test outputs: 4 DST1-MRD08SL-1

Note: The standard DS1T Safety I/O Terminals are equipped with spring-cage terminal blocks, but screw terminal blocks are available if desired, e.g., to replace previous terminals. Refer to Device Net Safety Accessories. *Use the Network Configurator Ver. 2.0 or later to make DST1-XD0808SL-1 settings.

Specifications Certified Standards Specifications Certification

Standard Model

body DST1- DST1- DST1- DST1- ID12SL-1 MD16SL-1 MRD08SL-1 XD0808SL-1

EN ISO 13849-1 Item

EN ISO 13849-2

Communications

IEC 61508

TÜV Rheinland power supply 11 to 25 VDC supplied via communications connector

EN 62061

voltage

EN 61131-2

IEC 61326-3-1 I/O power supply

20.4 to 26.4 VDC (24 VDC −15%/+10%)

voltage

UL508

ISA12.12.01 (excluding the DST1-MRD08SL-1) Commu-

UL1998 nications 24 VDC 24 VDC 24 VDC 24 VDC IEC 61508-3 power 100 m A 110 m A 100 m A 110 m A

Current

supply

24 VDC 24 VDC 24 VDC

sump-

tion 24 VDC

power (Input) (Input) (Input)

supply * 130 m A 130 m A 130 m A

(Output) (Output) (Output)

Overvoltage

category Noise immunity Conforms to IEC61131-2. Vibration 10 to 57 Hz: 0.35-mm single amplitude, 57 to 150 Hz: resistance 50 m/s2

Shock resistance 150 m/s2, 11 ms

ms ms

Mounting method 35-mm DIN Track Ambient operating

−10 to 55°C

temperature

10% to 85% 10% to 95%

Ambient operating 10% to 95% (with no

(with no (with no

humidity condensation)

condensation) condensation)

Ambient storage

−40 to 70°C

temperature Degree of protection IP20 Weight 420 g 600 g 420 g

*Not including power consumption for external devices.

Page Summary Contents For OMRON Safety I O Terminal DST1 Series Data Sheet

Page 1 Safety I/O Terminals DST1 Series CSM_DST1 Series_DS_E_7_4 Distributed Safety Terminals That Reduce Wiring. Lineup includes four models to accommodate various I/O types and number of I/O points. Monito...
Page 2 DST1 Series Safety Input Specifications Safety Output Specifications (Common with the DST1 Series) (Relay Output) Input type Sinking inputs (PNP) (DST1-MRD08SL-1) ON voltage 11 VDC min. Applicable rel...
Page 3 DST1 Series DST1-MD16SL-1 DC-DC Converter DST1-XD0808SL-1 (Non-insulated) Internal Circuits CAN H Shield CAN L Test Output Input Power Safety Input Circuit Output Power Safety Output Circuit Circuit S...
Page 4 DST1 Series Dimensions (Unit: mm) DST1-ID12SL-1 DST1-MD16SL-1 DST1-XD0808SL-1 DST1-MRD08SL-1 Safety Precautions Refer to the "Safety Precautions for All CIP Safety on Device Net Systems" for...
Page 5 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questi...

Manual Details

Brand Omron
Pages 5
File Size 976.13 KB
Published June 05, 2026
37 views

Enter the captcha to get the download link:

captcha

Frequently Asked Questions

Which model supports logic operation functions for partial safety system stopping?

The DST1-XD0808SL-1 also supports logic operation functions for high-speed processing.

What are the required certifications for these distributed terminals?

They are certified to EN954-1 (Cat.4), ISO13849-1 (PLe), and IEC 61508 SIL3.

What software is needed to configure the DST1-XD0808SL-1 settings?

Use the Network Configurator Ver. 2.0 or later for configuring the DST1-XD0808SL-1.

Are screw terminal blocks available if I need an alternative mounting option?

Yes, standard units use spring-cage terminals, but screw terminal blocks are available if desired.