Lenze Inverters - Frequency inverters MC frequency inverters MC1000 frequency inverters

Summary

This comprehensive guide details integrating MC 1000 and MC 3000 Series Variable Frequency Drives into a structured Modbus network system. It provides engineers and technicians with full reference coverage of necessary registers, including setup parameters, operational status monitoring, speed control, and advanced programming functions over Modbus. This document is essential for proper installation, configuration, and seamless remote control of the drive within industrial automation systems.

📄 Preview PAGE OF 35

Page 1 Text Content

MC Series Drives

Modbus Communications Reference Guide

Page Summary Contents For Lenze Inverters - Frequency inverters MC frequency inverters MC1000 frequency inverters

Page 1 MC Series Drives Modbus Communications Reference Guide
Page 2 About These Instructions This documentation applies to the use of an MC 1000 Series and an MC 3000 Series Variable Frequency Drive in a Modbus Network and should be used in conjunction with the MC Ser...
Page 3 Contents 1 Safety Information .............................................................................................................1 1.1 Warnings, Cautions and Notes .............................
Page 4 Contents 5 MC Drive Control Registers ................................................................................................10 5.1 Abbreviations ................................................
Page 5 Safety Information 1 Safety Information 1.1 Warnings, Cautions and Notes 1.1.1 General Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and ro...
Page 6 Safety Information 1.1.4 Electrical Connection When working on live drive controllers, applicable national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical ins...
Page 7 Introduction 2 Introduction This document defines the specifics required for Modbus serial communication with a Lenze-AC Tech standard MC 1000 or MC 3000 Series drive for control, status monitoring, a...
Page 8 Introduction 16 Preset Multiple Registers (4X references). Although the function is for multiple registers, we will accept only a single register to be written. Note: Since we do not differentiate bet...
Page 9 Data & Register Format 3 Data Representation - Internal and External 3.1 Register Format All registers are 16 bits. The data within these registers can take on the following forms: • Individual bi...
Page 10 Drive Setup & Operation 4 MC Drive Setup & Operation 4.1 Serial Address All AC Tech drives have a Serial Address Parameter that must be programmed prior to attempting to operate the serial int...
Page 11 Drive Setup & Operation Table 5: Control (Parameter #30) MC1000 MC3000 Setting Description Setting Description LOCAL (default) LOCAL (default) REMOTE REMOTE BOTH SERIAL KEYPAD TB STRIP KEYPAD 2 Al...
Page 12 Drive Setup & Operation 4.6 Watchdog Timer All AC Tech drives are equipped with a Serial Link “Watchdog Timer”. If the Modbus Master wishes to control the drive (start, stop, forward, reverse, etc...
Page 13 Drive Setup & Operation 4.7 Monitoring Only Operation 1. Power up drive with serial enabled. 2. Simply read AC Tech Register #24 (Modbus Register #25) or any other readable register. 3. No unlocki...
Page 14 Drive Control & Communication AC T# (H EX 5 MC Drive Control Registers re pr es en ta tio n) Table 6 describes the MC Drive Control Registers in ascending order of AC Tech Register #. The HEX repr...
Page 15 Drive Control & Communication AC T# (H EX re pr es en ta tio n) [NOTE] REGISTER NAME MESSAGE MIN MAX UNITS or Section SA CRCH CRCL Local PID Command RS SA DH DL CRCH CRCL 41 (29) Refer to Section ...
Page 16 Drive Control & Communication 5.2 Drive Control - Register #1 Table 8 illustrates the Data format of Register #1, Drive Control. Table 8: Drive Control - Register #1 Bit Command UPDATE BUFFERS LOC...
Page 17 Drive Control & Communication 5.3 Drive Size - Register #21 Table 9 lists the MC1000 and MC3000 Series drives. Register 21 will contain the value in the "Size" column. Table 9: Drive Siz...
Page 18 Drive Control & Communication 5.4 Drive Status - Registers #24-29 5.4.1 Reading Register #24 When reading register #24, the number of wordscan either be 1 or 6. This is an exception to the rule of...
Page 19 Drive Control & Communication 5.4.2 Operational Status - Registers #24 & 26 Table 11 lists the Operational Status (byte D3L) Table 11: Operational Status - Register #26 Setting Parameter FAULT...
Page 20 Drive Control & Communication 5.4.5 Speed Command Source - Registers #24 & 28 Table 14 lists the Speed Command Source (Register #24 byte D5H or Register #28 DH). Table 14: Speed Command Source...
Page 21 Drive Control & Communication 5.4.7 Present Fault - Registers #24 & 29 Table 16 lists the Present Fault (Register #24 byte D6H or Register #29 DH) Table 16: Present Fault Setting Fault Display...
Page 22 Drive Control & Communication 5.6 Keypad Speed - Register #40 This register enables the user to set the keypad speed to desired value. • Range is 0 - 65000 in hundredths of a Hz • Most significant...
Page 23 Drive Control & Communication 5.12 Register Version Register Version is the number to identify if current version of software has any register changes relative to previous versions: a register has...
Page 24 Drive Control & Communication 6 MC Programming Parameters 6.1 Format NOTE - Attention Parameter list presented in Section 6.2 is valid only for MC Software revision 213-083. For revisions, refer t...
Page 25 Drive Control & Communication 6.2 Parameter List AC Tech Parameter Name Range of Adjustment Factory Default Register Modbus value (decimal value) Number Pa ra et er (hexadecimal representation) 51...
Page 26 Drive Control & Communication AC Tech Parameter Name Range of Adjustment Factory Default Register Modbus value (decimal value) Number (hexadecimal representation) Pa ra et er 76 (4C) 25 2,3 START ...
Page 27 Drive Control & Communication AC Tech Parameter Name Range of Adjustment Factory Default Register Modbus value (decimal value) Number (hexadecimal representation) Pa ra et er 82 (52) 31 3,4 UNITS ...
Page 28 Drive Control & Communication AC Tech Parameter Name Range of Adjustment Factory Default Register Modbus value (decimal value) Number (hexadecimal representation) Pa ra et er 98 (62) TB13A 00 - No...
Page 29 Drive Control & Communication AC Tech Parameter Name Range of Adjustment Factory Default Register Modbus value (decimal value) Number (hexadecimal representation) Pa ra et er 103 (67) 52 3,4 TB14O...
Page 30 Drive Control & Communication NOTE 4 - Acceleration Limits Acceleration Limits HP Adjustment Range .025 - 20 1 - 36000 (0.1 - 3600 sec) 25 - 60 3 - 36000 (0.3 - 3600 sec) NOTE 5 - Deceleration Lim...
Page 31 Drive Control & Communication NOTE 10 - PROGRAM (Register 116) "RST HIGH" will appear as another option on drives that are configured for high frequency. NOTE 11 - LANGUAGE (Register 150...
Page 32 Drive Control & Communication 7 Quick Start Instructions Follow these Quick Start instructions to use Mod Bus Communications for basic network control of an MC drive. These instructions are a repr...
Page 33 Drive Control & Communication Unlocking the Drive: 1. The first write necessary to the drive to perform any function (start,change speed, change a parameter, etc) needs to be an unlock command. To...
Page 34 Drive Control & Communication 7.4 Basic Drive Status AC Tech register 24 is a 6 word entity containing the drive’s status information. To retrieve the entire status block (Modbus registers 24-29) ...
Page 35 Lenze AC Tech Corporation 630 Douglas Street • Uxbridge MA 01569 • USA Sales: 800-217-9100 •Service: 508-278-9100 www.lenze-actech.com RG-MCMOD-e5

Manual Details

Brand Lenze
Pages 35
File Size 145.83 KB
Published June 03, 2026
56 views

Enter the captcha to get the download link:

captcha

Frequently Asked Questions

What manual should I use with this Modbus guide?

Use the MC Series Installation and Operation Manual (Document M101 or M301) that shipped with your drive.

How do I change an acceleration time using Modbus?

Find the associated Modbus register number by adding 52 to the MC parameter number. For example, write the desired time into Modbus register 40060.

What is the Modbus address for controlling speed?

Set Parameter 29 (MANUAL) to KEYPAD and then write the speed to Keypad Speed Command Register, which is Modbus register 40041.

How can I read the drive's full operational status block?

Send a read command for an entire status block by reading from Modbus register 40025 using function code 03 with a register count of 6.