Delta Industrial Automation PLC Programmable Controller ADP485-01 RS485 Adapter Installation Manual

Summary

The ADP485-01 is a versatile interface converter designed for establishing stable RS-485 communication links between various Delta industrial products, including PLCs, HMIs, VFDs, and servo drives. Featuring integrated surge absorption, overcurrent protection, and optional termination resistors, it ensures reliable connectivity across diverse automation systems. This manual serves as a comprehensive guide for engineers and technicians, detailing critical installation warnings, environmental specifications, detailed wiring schematics (COM1, COM2, RJ12), and best practices for proper network configuration and cable management in industrial settings.

📄 Preview PAGE OF 2

Page 1 Text Content

Environmental Specification 繁體中文

RS-485 Network Connection with Delta Products

ADP485-01 VFD (AC Motor Drive) Environment 本機為開放型 (Open Type) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電

Operation 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), pollutant degree 2 擊或衝擊意外之外殼配線箱內。另必須具備保護措施 (如: 特殊之工具或鑰匙才可打開) 防止非維護 人員操作或意外衝擊本體,造成危險及損壞。請勿在上電時觸摸任何端子。

Storage -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

在串聯通訊各個節點所連接之裝置,其通訊速率 (Baud rate) 及通訊格式 (Format) 必須設定相同以

Vibration/Shock International Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC

及每個節點必須有獨立之站號位址 (Unit address)。

resistance 68-2-27 (TEST Ea)

出/入配線端子鏍絲扭力為 1.95kg-cm (1.7 in-lbs),只能使用 60°C/75°C 之銅導線。

COM1, COM2, and RJ12 PIN Explanation

COM1-DB9 female RJ12-VFD

本產品為一轉接器,主要用於台達機電產品 RS-485串聯通訊連接之用,本轉接器內建有突波吸收及限

流保護裝置,對於連接於ADP485-01的裝置,供了更好的保護。另外並提供終端電阻 (120Ω) 選擇開關, 不需外加。因此本產品提供台達機電產品在RS-485連線、保護及應用非常方便的介面轉接器。

RS-485 network

ADP485-01提供四種不同型式之插座以搭配台達機電產品 PLC DVP系列、人機介面 DOP系列、變頻器 PIN Definition PIN Definition VFD系列、伺服驅動器ASD系列使用,提供相互間 RS485通訊連線使用。

1 RS485- 1 +15V 產品外觀 6, 2 RS485+ 2 GND

3 RS485+ 3 SG- 4 RS485- 4 SG+ 5, 6, 7, 8, 9: NC 5, 6: Reserved

ADP485-01 DOP (HMI)

HMI DOP Series COM2-DB9 male RJ12-ADP485-01

DB9 male connector DB9 male connector F3

COM1 COM2 PIN Definition PIN Definition 尺寸單位:mm

one by one wiring

connect to COM 1 3, 6 RS485- 3 RS-485+

固定板 5 終端電阻選擇開關(出廠設定值為 OFF

8 RS485+ 4 RS-485-

5, 9 GND 5 GND COM1 (DB9 母座) 6 DIN 軌糟 (35mm) 1, 2, 4, 7: NC 1, 2, 6: NC COM2 (DB9 公座) 7 RS-485 連接口

RS-485 network 銘牌 8 RJ12 連接口(連接變頻器)

Use of Terminating Resistance

In all RS-485 installations, the cable must be correctly terminated with two sets of resistors, one set at

each end of the network (4,000 feet maximum total cable length). This applies even if you are only ADPCAB03A:ADP485-01 台達伺服驅動器 ASD-A 連接線/30 公分 using one slave node connected to one master device. The terminating resistors prevent reflection ADPCAB03B:ADP485-01 台達伺服驅動器 ASD-B 連接線/30 公分

problems that can interfere with data transmission. The resistance value of the terminating resistors should match the characteristic impedance of the cable. A typical value is 120 ohms. The terminating resistors must be placed at the two farthest ends of the RS-485 network, regardless of where the

ENGLISH ADP485-01 ASD-A (Servo Drive) master device is. In some cases master device RS-485 ports have built in or optional terminating

台達機電產品 RS-485 網路連接圖

Warning resistors. Beware of your network (whether it has one node or 32 nodes) having only two sets of ADP485-01 is an OPEN-TYPE. Please place the module in an enclosure away from airborne dust or high terminating resistors. ADP485-01 VFD 變頻器

humidity and prevent electric shock or sudden shock on ADP485-01. Also, it is equipped with protective Termination Resistor Switch

VFD Series

method such as some special tool or key to open the enclosure, so as to avoid the hazard to users or any damage to the module. Do NOT touch terminals when power on. When many devices are connecting in serial, their Baud rate and communication format setting should be the same. Also, each device must have individual Unit Address.

Connecting cable (ADPCAB03A)

I/O terminal screw should be tightened between 1.95kg-cm (1.7 in-lbs). Use copper conductor only, 60/75°C.

Introduction RJ12

ADP485-01 is mainly designed to connect Delta product by RS-485 interface. It is equipped with surge RS-485 network

absorber and limited current protection to ensure safe connection of different devices. Also, 120Ω RS-485網路 terminating resistance selection is available. This module enables Delta products to connect one another by RS-485 interface with much concern of safety and wide application. Cable Connection ADP485-01 offers four different connectors to enable the network connection for Delta’s PLC DVP

series, HMI DOP series, AC Motor Drive VFD series and Servo drive ASD series. ADPCAB03A

Product Profile

ADP485-01 ASD-B (Servo Drive)

DB9 male 1394 male ADP485-01 DOP 人機介面

人機介面 DOP

4RS485 -

GND F1

DB9公頭DB9公頭 F3

Connecting cable (ADPCAB03B) RS485 +

Unit: mm COM1 COM2

ADPCAB03B

連接於 COM 1

1 Mounting plate 5 ON/OFF of terminating resistor (default setting: OFF) 2 COM1 (DB9 female) 6 DIN rail (35mm)

3 COM2 (DB9 male) 7 RS-485 port RS-485 network

DB9 male Mini DIN RS-485網路

4 Nameplate 8 RJ12

Optional Connecting Cable

ADPCAB03A: ADP485-01 ASD-A connecting cable/30cm GND RS485 -

ADPCAB03B: ADP485-01 ASD-B connecting cable/30cm

RS485 +

Page Summary Contents For Delta Industrial Automation PLC Programmable Controller ADP485-01 RS485 Adapter Installation Manual

Page 1 Environmental Specification 繁體中文 RS-485 Network Connection with Delta Products ADP485-01 VFD (AC Motor Drive) Environment 本機為開放型 (Open Type) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電 Operation 0°C ~ 55°C (tempe...
Page 2 ADP485-01 ASD-A 伺服驅動器 RS-485 环境规格 ADP485-01 VFD 变频器 环境规格 2. 储存:-25°C ~ 70°C(温度),5 ~ 95%(湿度) 国际标准规范 IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) 連接線ADPCAB03A COM1, COM2及RJ1...